  System #   Description F Rating Product
CAJ1109-W - Max. 4 in. steel or copper pipe, or EMT w/ max. 10 in. diameter opening 2 hr. FSM 22
CAJ1212-W - Up to 4, max. 4 in. steel or copper pipe, or EMT w/ max. 36 x 36 in. opening 2 hr. FSM 22
CAJ1235-W - Max. 24 in. steel, max. 6 in. copper, or max. 4 in. EMT w/ max. 26 in. diameter opening 2 & 3 hr. FS 1900 or 900+
CAJ1236-W - Max. 12 in. steel or iron, max. 6 in. copper, or max. 4 in. EMT w/ max. 16 in. diameter opening 3 hr. FS 3000
CAJ1242-W - Up to 6, max. 1 in. flexible steel conduit w/ max. 6 in. diameter opening 3 hr. FSP 1000
CAJ1379-W - Max. 24 in. steel or iron, or max. 4 in. EMT w/ max. 26-1/2 in. diameter opening 3 hr. FSP 900+
CAJ1387-W - Max. 10 in. steel, max. 6 in. conduit, or max. 4 in. EMT w/ max. 14 in. diameter opening 2 hr. FSP 1900
CAJ1402-W - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 10-3/4 in. diameter opening 2 hr. FSP 1900
CAJ1403-W - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening (one sided) 2 or 3 hr. FSP 900+ or FSP 1900
CAJ1404-W - Max. 24 in. steel, max. 6 in. copper or EMT w/ max. 24-7/8 in. diameter opening 2 hr. FSP 1900 or FSP 900+
CAJ1406-W - Up to 8, max. 6 in. steel or 4 in. copper, or max. 2 in. EMT w/ max. 15-1/4 in. opening 2 hr. FSP 900+
CAJ1426-W - Up to 24, max. 4 in. steel, iron, or EMT or 1-1/2 in. copper w/ max. 48 x 18 in. opening 2 hr. FSP 3000
CAJ1465-W - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening (Bottom install) 2 hr. FSP 1900
CAJ1466-W - Max. 12 in. steel pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max. 18 in. dia. opening. 3 hr. FlameSafe Silicone
CAJ1467-W - Max. 4 in. steel or iron, max. 4 in. copper or EMT w/ max. 6 in. dia. opening (Optional Steel Sleeve) 2 hr. FlameSafe Silicone
CAJ1468-W - Up to three max. 2 in. steel pipe or conduit or EMT w/ max. 6 in. diameter opening (Optional Steel Sleeve) 2 hr. FlameSafe Silicone
CAJ1469-W - Max. 12 in. steel pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max 16 in. dia. opening (Optional Steel Sleeve). 2 hr. FlameSafe Silicone
CAJ1470-W - Max. 24 in. steel or iron pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max. 26 in. dia. opening. 2 hr. FlameSafe Silicone
CAJ1502-W - Multiple max. 1-1/2 in. flexible metallic conduit w/max. 6 in. diameter opening. 2 or 3 hr. FS 900+ or FS 1900
CAJ1528-W - Max. 12 in. steel, iron or max. 4 in. copper w/ max. 14 in. diameter opening. T Rating - 2 HOUR 3 hr. FS 900+
CAJ1535-W - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening. (Bottom only) 3 hr. FS 1900
CAJ1565-W - Max. 4 in. metallic penetrant in max. 6 in. opening (Hollow Core Floor and W Rating) 1 or 2 hr. FS 4000
CAJ1566-W - Max. 4 in. metallic penetrant in max. 6 in. opening with optional steel or PVC sleeve (W Rating) 3 hr. FS 4000
CAJ1567-W - Max. 8 in. metallic penetrant in max. 10-1/2 in. opening with optional sleeve (W Rating) 2 or 3 hr. FS 4000
CAJ1568-W - Multiple max. 4 in. metallic penetrants in max. 216 square in. opening (W Rating) 2 hr. FS 4000
CAJ1569-W - Max. 8 in. metallic penetrant in max. 10-1/2 in. opening through thin walls/floors (W Rating) 2 hr. FS 4000
CAJ1570-W - Max. 10 in. metallic penetrants in max. 12 in. opening (T Rating 2 hr. & W Rating) 2 hr. FS 4000
CAJ1577-W - Max. 4 in. metallic penetrant through max. 6 in. PVC sleeve 3 hr. FS 1900 or FS 900+
CAJ1578-W - Max. 4 in. metallic penetrant through max. 6 in. PVC sleeve w/ point of contact 3 hr. FS 1900
CAJ1584-W - Multple max. 1-1/4 in. flexible steel gas piping in a 6 in. diameter opening 3 hr. FS 1900 or FS 900+
CAJ8121-W - Max.6 in. steel, cast iron, EMT or rigid conduits in max. 900 sq. in. opening w/ max. 30 in. dimension 2 & 4 hr. FS Composite Sheet

 

CBJ1035-W - Max. 24 in. steel, max. 6 in. conduit, or max. 4 in. EMT w/ max. 26 in. diameter opening 3 hr. FS 1900
WJ1031 - Max. 24 in. steel, max. 6 in. copper, or max. 4 in. EMT w/ max. 24-5/8 in. diameter opening 2 hr. FS 1900
WJ1065 - Max. 24 in. steel, max. 6 in. conduit, or max. 4 in. EMT w/ max. 26 in. diameter opening 2 hr. FS 1900 or FS 900+
WJ1066 - Multi pene., max. 2 in. steel, iron, or EMT w/ max. 33 sq. in. opening 2 hr. FS 1900
WJ1069 - Max. 4 in. steel, iron, or copper pipe, or EMT w/ max. 6-1/8 in. diameter opening 2 hr. FS 1900
WJ1087 - Up to 4, max. 1 in. flexible aluminum conduits w/ max. 4 in. diameter opening 2 hr. FS 1900
WJ1090 - Multi. Pene., max. 3 in. steel, iron, or EMT w/ max. 91 sq. in. opening 2 hr. FS 900+
WJ1137 - Max. 4 in. steel pipe or conduit or EMT w/ max. 5 in. dia. opening 2 hr. FlameSafe Silicone
WJ1158 - Multiple max. 1-1/2 in. flexible stell conduit w/ max. 6 in. diameter opening. 2 hr. FS 900+
WJ1206 - Multple max. 1-1/4 in. flexible steel gas piping in a 6 in. diameter opening 1 or 2 hr. FS 1900 or FS 900+
WJ1207 - Multple max. 1 in. metal pipes or condui in a 6x6 in. rectangular opening 1 or 2 hr. FSPIL

Concrete Floors

  System #   Description F Rating Product
CAJ1109-F - Max. 4 in. steel or copper pipe, or EMT w/ max. 10 in. diameter opening 2 hr. FSM 22
CAJ1212-F - Up to 4, max. 4 in. steel or copper pipe, or EMT w/ max. 36 x 36 in. opening 2 hr. FSM 22
CAJ1235-F - Max. 24 in. steel, max. 6 in. copper, or max. 4 in. EMT w/ max. 26 in. diameter opening 2 & 3 hr. FS 1900 or FS 900+
CAJ1236-F - Max. 12 in. steel or iron, max. 6 in. copper, or max. 4 in. EMT w/ max. 16 in. diameter opening 3 hr. FS 3000
CAJ1242-F - Up to 6, max. 1 in. flexible steel conduit w/ max. 6 in. diameter opening 3 hr. FS 1000
CAJ1379-F - Max. 24 in. steel or iron, or max. 4 in. EMT w/ max. 26.5 in. diameter opening 3 hr. FS 900+
CAJ1387-F - Max. 10 in. steel, max. 6 in. conduit, or max. 4 in. EMT w/ max. 14 in. diameter opening (2-1/2 in. slab) 2 hr. FS 1900
CAJ1402-F - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 10-3/4 in. dia. opening (2-1/2 in. slab) 2 hr. FS 1900
CAJ1403-F - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening (one sided) 2 or 3 hr. FS 900+ or FS 1900
CAJ1404-F - Max. 24 in. steel, max. 6 in. copper or EMT w/ max. 24-7/8 in. diameter opening (2-1/2 in. slab) 2 hr. FS 1900 or 900+
CAJ1406-F - Up to 8, max. 6 in. steel or 4 in. copper, or max. 2 in. EMT w/ max. 15-1/4 in. opg. (2-1/2 in. slab) 2 hr. FS 900+
CAJ1426-F - Up to 24, max. 4 in. steel, iron, or EMT or 1-1/2 in. copper w/ max. 48 x 18 in. opening 2 hr. FS 3000
CAJ1465-F - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening (Bottom install) 2 hr. FS 1900
CAJ1466-F - Max. 12 in. steel pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max. 18 in. dia. opening. 3 hr. FlameSafe Silicone
CAJ1467-F - Max. 4 in. steel or iron, max. 4 in. copper or EMT w/ max. 6 in. dia. opening (Optional Steel Sleeve) 2 hr. FlameSafe Silicone
CAJ1468-F - Up to three max. 2 in. steel pipe or conduit or EMT w/ max. 6 in. diameter opening (Optional Steel Sleeve) 2 hr. FlameSafe Silicone
CAJ1469-F - Max. 12 in. steel pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max 16 in. dia. opening (Optional Steel Sleeve). 2 hr. FlameSafe Silicone
CAJ1470-F - Max. 24 in. steel or iron pipe, max. 6 in. steel conduit or max. 4 in. EMT w/ max. 26 in. dia. opening. 2 hr. FlameSafe Silicone
CAJ1502-F - Multiple max. 1-1/2 in. flexible metallic conduit w/max. 6 in. diameter opening. 2 or 3 hr. FS 900+ or FS 1900
CAJ1528-F - Max. 12 in. steel, iron or max. 4 in. copper w/ max. 14 in. diameter opening. T Rating - 2 HOUR 3 hr. FS 900+
CAJ1535-F - Max. 8 in. steel or iron, max. 4 in. copper or EMT w/ max. 9-5/8 in. dia. opening. (Bottom only) 3 hr. FS 1900
CAJ1565-F - Max. 4 in. metallic penetrant in max. 6 in. opening (Hollow Core Floor and W Rating) 1 or 2 hr. FS 4000
CAJ1566-F - Max. 4 in. metallic penetrant in max. 6 in. opening with optional steel or PVC sleeve (W Rating) 3 hr. FS 4000
CAJ1567-F - Max. 8 in. metallic penetrant in max. 10-1/2 in. opening with optional sleeve (W Rating) 2 or 3 hr. FS 4000
CAJ1568-F - Multiple max. 4 in. metallic penetrants in max. 216 square in. opening (W Rating) 2 hr. FS 4000
CAJ1569-F - Max. 8 in. metallic penetrant in max. 10-1/2 in. opening through thin walls/floors (W Rating) 2 hr. FS 4000
CAJ1570-F - Max. 10 in. metallic penetrants in max. 12 in. opening (T Rating 2 hr. & W Rating) 2 hr. FS 4000
CAJ1577-F - Max. 4 in. metallic penetrant through max. 6 in. PVC sleeve 3 hr. FS 1900 or FS 900+
CAJ1578-F - Max. 4 in. metallic penetrant through max. 6 in. PVC sleeve w/ point of contact 3 hr. FS 1900
CAJ1584-F -- Multple max. 1-1/4 in. flexible steel gas piping in a 6 in. diameter opening 3 hr. FS 1900 or FS 900+
CAJ8121-F - Max.6 in. steel, cast iron, EMT or rigid conduits in max. 900 sq. in. opening w/ max. 30 in. dimension 2 & 4 hr. FS Composite Sheet
FA1095 - Max. 8 in. metallic penetrant in max. 10-1/2 in. opening, min. 2-1/2 in. thick concrete floor (W Rating) 2 hr. FS 4000

Wood Framed Chase Walls and Floors

  System #   Description F Rating Product
FC1020 - Max. 4 in. steel pipe or EMT, or max. 3 in. copper pipe w/ max. 5-1/2 in. diameter opening 1 & 2 hr. FS 1900
FC1037 - Up to 3, max. 1 in. flexible steel conduit w/ max. 2 in. diameter opening 1 & 2 hr. FS 1900
FC1084 - Max. 4 in. steel pipe or EMT, or max. 3 in. copper pipe w/ max 5 in. diameter opening 1 & 2 hr. FS 900+
FC1107 - Max. 4 in. steel pipe, steel conduit, iron, or EMT or max. 2 in. copper w/ max. 5 in. diameter opening 2 hr. FlameSafe Silicone
FC1110 - Max. 4 in. steel pipe, steel conduit, iron, or EMT or max. 2 in. copper w/ max. 5 in. dia. opening (Chase) 1 & 2 hr. FlameSafe Silicone
FC1125 - Multiple max. 1-1/2 in. flexible metallic conduit w/ max. 4 in. diameter opening 1 & 2 hr. FS 900+

Steel Framed Concrete Floors

  System #   Description F Rating Product
FE1005 - Max. 4 in. steel pipe or EMT, or max. 3 in. copper pipe w/ max. 5 in. diameter opening 1 hr. FS 900+
FE1006 - Up to 3, max. 1 in. flexible steel conduit w/ max. 2 in. diameter opening 1 hr. FS 1900

Gypsum Walls

  System #   Description F Rating Product
WL1046 - Max.1/2 in. flexible steel or aluminum conduit w/ max. 1-3/8 in diameter opening 1 & 2 hr. FS 1900 or FS 900+
WL1152 -

Max 24 in. steel pipe, 6 in. copper pipe, or 4 in. EMT w/ max. 26+ in. diameter opening

1 & 2 hr. FS 1900 or FS 900+
WL1153 - Multi pene., max. 2 in. steel, iron, or EMT w/ max 33 sq. in. opening 1 & 2 hr. FS 1900
WL1204 - Up to 4, max. 1 in. flexible aluminum conduits w/ max. 4 in. diameter opening 1 & 2 hr. FS 1900
WL1207 - Multi pene., max. 3 in. steel, iron, or EMT w/ max 91 sq. in. opening 1 & 2 hr. FS 900+
WL1312 - Max. 4 in. steel pipe, steel conduit, or EMT w/ max. 5 in. diameter opening 1 & 2 hr. FlameSafe Silicone
WL1343 - Multiple max. 1-1/2 in flexible steel conduit w/ max. 6 in diameter opening 1 & 2 hr. FS 900+
WL1404 - Max. 24 in. steel pipe, 6 in. copper pipe, or 4 in. EMT w/ sheet metal or steel sleeve 1 & 2 hr. FS 1900 or FS 900+
WL1427 - Multiple max. 1-1/4 in. flexible steel gas piping in a 6 in. diameter opening 1 & 2 hr. FS 1900 or FS 900+
WL1428 - Multiple max. 1 in. metal pipes or conduit in a 6x6 in. rectangular opening 1 & 2 hr. FSPIL